EN 13501-2 · ASTM E119 · ISO 834
Fire Rated Glass Calculator
EWEIEW Glass
Limits radiant heat to ≤ 15 kW/m². Unexposed face CAN get hot. Good for facades & atriums.
EI Glass
Full insulation. Unexposed face rise ≤ 140°C avg above ambient. Required in escape routes.
Formula
ISO 834: T = 345 × log₁₀(8t + 1) + 20°C | EI limit: +140°C avg / +180°C max above ambient | EW: typically 60–65% of furnace temp
Furnace / Fire Side
EW — Unexposed Face
EI — Unexposed Face
EI Safety Limit (160°C)
EW Glass
Unexposed Temp586°C
vs Furnace62% of furnace
Rise above 20°C+566°C
Rad. Flux limit≤ 15 kW/m²
InsulationNOT RATED
EI Glass
Unexposed Temp123°C
vs Furnace13% of furnace
Rise above 20°C+103°C
Max allowed rise+140°C avg
CompliancePASS ✓